powernet(8) Network UPS Tools (NUT) powernet(8)NAME
powernet - Driver for APC SNMP UPS equiment
NOTE
This man page only documents the hardware-specific features of the powernet driver. For information about the core driver, see nutups-
drv(8).
SUPPORTED HARDWARE
APC AP9606 APC Web/SNMP management card, perhaps others
EXTRA ARGUMENTS
This driver supports the following optional settings in the ups.conf(5):
community=value
SNMP community to use (default = public)
sdtype=value
Shutdown type to use - possible values:
0 = Soft shutdown or powerdown, depending on line status (default)
1 = Soft shutdown followed by powerdown
2 = Instant shutdown
3 = Shutdown with grace period
REQUIREMENTS
You will need to install the Net-SNMP package from http://www.net-snmp.org/ before building this driver.
INSTALLATION
This driver is not built by default. You can build it by using "configure --with-drivers=powernet" before calling make.
IMPLEMENTATION
The hostname of the UPS is specified with the "port" value in ups.conf, i.e.:
[ap9606]
driver = powernet
port = apc-snmp-ups.example.com
community = writable
AUTHORS
Dmitry Frolov (powernet)
Hans Ekkehard Plesser (snmp-ups)
Arnaud Quette (snmp-ups)
SEE ALSO
APC's PowerNet MIB v3.3.0
Available online at http://apcc.com/tools/download/
The core driver:
nutupsdrv(8)
Internet resources:
The NUT (Network UPS Tools) home page: http://www.exploits.org/nut/
NUT mailing list archives and information: http://lists.exploits.org/
Tue Oct 22 2002 powernet(8)
Check Out this Related Man Page
snmp-ups(8) Network UPS Tools (NUT) snmp-ups(8)NAME
snmp-ups - Driver for RFC 1628 SNMP UPS equipment
NOTE
This man page only documents the hardware-specific features of the snmp-ups driver. For information about the core driver, see nutups-
drv(8).
SUPPORTED HARDWARE
Any UPS that is RFC 1628 (UPS MIB) compliant.
EXPERIMENTAL DRIVER
This driver has been tagged experimental and is not built by default.
REQUIREMENTS
This driver needs UCD SNMP, aka Net-SNMP installed to compile successfully. See http://www.net-snmp.org/ for more information.
On Red Hat 7.2, these packages are required:
ucd-snmp-devel-4.2.3-1, ucd-snmp-4.2.3-1, ucd-snmp-utils-4.2.3-1
You must install SNMP-UPS-MIB.txt in your MIBs directory - typically /usr/share/snmp/mibs/, but it may vary from system to system. You can
generate this from chapter 4 of RFC 1628 (see http://www.faqs.org).
EXTRA ARGUMENTS
This driver supports the following optional settings in the ups.conf(5):
community=name
Set community name (default = public)
snmp_version=version
Set SNMP version (default = v1, the other allowed value is v2c)
INSTALLATION
This driver is not built by default. You can build it by using "configure --with-drivers=snmp-ups" before calling make.
IMPLEMENTATION
The hostname of the UPS is specified with the "port" value in ups.conf, i.e.:
[snmp]
driver = snmp-ups
port = snmp-ups.example.com
community = public
snmp_version = v1
SUPPORTED VARIABLES
INFO_MFR UPS Manufacturer
INFO_MODEL UPS Model
INFO_FIRMREV Firmware/Software Version
INFO_STATUS OFF, OL, OB, BOOST, TRIM
INFO_BATTPCT Battery percentage
INFO_RUNTIME Predicted runtime on battery
INFO_BATTVOLT Battery Voltage
INFO_OUTVOLT Output Voltage
PLANNED SUPPORT
INFO_UTILITY Input Voltage
INFO_ACFREQ AC Frequency
INFO_UPSTEM UPS Temperature
INFO_LOADPCT Load Percentage
CMD_? Not determined
AUTHORS
Arnaud Quette, Hans Ekkehard Plesser
SEE ALSO
The core driver:
nutupsdrv(8)
Internet resources:
The NUT (Network UPS Tools) home page: http://www.exploits.org/nut/
NUT mailing list archives and information: http://lists.exploits.org/
Tue Oct 22 2002 snmp-ups(8)