Operating Systems Solaris Sun Fire X4540 in a reboot cycle Post 302554091 by genkuro on Saturday 10th of September 2011 12:41:42 AM
Old 09-10-2011
Sun Fire X4540 in a reboot cycle

So I have a lot of equipment in San Diego racks and there was a recent county-wide black out. Our data racks are supposedly on diesel generators. Most everything made it through the outage just fine without any issue.

But for whatever reason, one of our X4540's developed a quirky habit of rebooting itself constantly. It powers on and resets itself 1 second to 10 minutes later. This can happen as early as early as the BIOS splash screen (common) and as late as Solaris completely running (rare). It's not uncommon for a reset to occur during the memory check. But I'm cautious in reading too much into this.

I read the docs just briefly. And they do hint that the power supplies will restart or shutdown the system if power isn't within spec. I tried every permutation of multiple PDUs/powering left,right, or both power supplies and it made no difference whatsoever.

On the suggestion from Oracle support, I reseated just about every user serviceable component on the machine. And this didn't do much at all either.

Has anyone ever seen anything like this from a Sun Fire? Any help GREATLY appreciated.

Thanks,
Brian
 

6 More Discussions You Might Find Interesting

1. UNIX for Advanced & Expert Users

Sun Fire v1280 is crashing

I still haven't got an answer to this question... Excerpt from My SysAd Blog A colleague of mine is having a problem with a Sun Fire v1280 server crashing. He tried Googling for the error message in red but hasn't found anything yet. Your insights would be greatly appreciated. "cannot... (2 Replies)
Discussion started by: esofthub
2 Replies

2. UNIX for Dummies Questions & Answers

Sun Fire 280R

Hello all, I'm lost and can't figure this problem out. I have a Sun fire 280R running Solaris 8. Everything was working great. I have one drive in bay 1(not 0). But when I reboot the system it trys to open files in /dev/rdsk/c1t1d0s0. Should it have been opeing /dev/rdsk/c1t0d0s0, the... (4 Replies)
Discussion started by: larryase
4 Replies

3. Solaris

Sun Fire 280R Sun Solaris CRT/Monitor requirements

I am new to Sun. I brought Sun Fire 280R to practice UNIX. What are the requirements for the monitor/CRT? Will it burn out old non-Sun CRTs? Does it need LCD monitor? Thanks. (3 Replies)
Discussion started by: bramptonmt
3 Replies

4. Solaris

Sun X4540 Ilom - Solaris 10

Hello Admins, I am trying to access the solaris 10 host using the ilo. When I do start /SP/console, it just hangs, it doesn't give me any login prompt... I tried reset /SYS and also did reset /SP...but no luck... We have Sun X4540.... Any help appreciated..Thanks (9 Replies)
Discussion started by: snchaudhari2
9 Replies

5. Hardware

Sun fire 4270 reset BIOS settings after reboot

Hello, I am trying to perform Suse 10 SP3 installation via network in 6 Sun Fire 4270 M2 servers. The problem is that even if i set first prio boot device the hard disk the system always try to boot from network.And after the first restart the BIOS setting has been lost(and PXE come first... (2 Replies)
Discussion started by: @dagio
2 Replies

6. Solaris

Sun fire x2270

Hello, I have purchaced an old SUn fire x2270 server . I wanted to make ILOM upgrade to the latest version of software : ILOM 3.0.9.18.a r126592 BIOS vers. 2.09 Server 2.2.3 (10-Aug-2018) Because my version is very outdated. But i can't download the updatebecause it's require... (4 Replies)
Discussion started by: LouisLakoute
4 Replies
ONEAC(8)							    NUT Manual								  ONEAC(8)

NAME
oneac - Driver for Oneac UPS equipment NOTE
This man page only documents the hardware-specific features of the oneac driver. For information about the core driver, see nutupsdrv(8). SUPPORTED HARDWARE
This driver supports various Oneac UPS families: o EG (late 80s, early 90s, plug-in serial interface card) o ON (early and mid-90s, plug-in serial interface card) o OZ (mid-90s on, DB-25 std., interface slot) o OB (early 2000's on, big cabinet, DB-25 std., interface slot) If your UPS is equipped with the Basic Interface card, use the genericups(8) driver. EXTRA ARGUMENTS
This driver supports the following optional settings in the ups.conf(5) file: testtime=num Change battery test time from the 2 minute default. offdelay=num Change shutdown delay time from 0 second default. INSTANT COMMANDS
This driver supports the following Instant Commands. (See upscmd(8)) All UPS units shutdown.return Turn off the load possibly after a delay and return when power is back. shutdown.stop Stop a shutdown in progress. shutdown.reboot Shut down the load briefly while rebooting the UPS. test.failure.start Starts a 15 second long simulation of an input power failure. test.battery.start.quick Start a "quick" battery test. The default time is 2 minutes. This time can be set in the ups.conf file. See testime above. test.battery.stop Stops a battery test that is in progress. All ON UPS units reset.input.minmax Reset the minimum and maximum input line voltage values seen since the last reset or power on. Newer ON UPS units test.panel.start Start testing the UPS panel. test.battery.start.deep Start a "deep" battery test. This test runs the UPS until the low battery point and then returns to the AC line. reset.input.minmax Reset the minimum and maximum input line voltage values seen since the last reset or power on. beeper.enable Enable UPS beeper/buzzer. beeper.disable Disable UPS beeper/buzzer. beeper.mute Mutes the UPS beeper/buzzer for the current alarm condition(s). WRITABLE VARIABLES
See upsrw(8) to see what variables are writable for the UPS. Note If your UPS supports writing battery.runtime.low, the new set value is to be entered in minutes (up to 99) but the reported value is reported in seconds (set value * 60). Note If your UPS supports input.transfer.low and input.transfer.high, those values are used to create an allowable output range. The UPS will do what it can to keep the output voltage value within the defined range (for example: tap change or switch to inverter). AUTHOR
Bill Elliot <bill@wreassoc.com>, Eric Lawson <elawson@inficad.com> SEE ALSO
The core driver: nutupsdrv(8) Internet resources: The NUT (Network UPS Tools) home page: http://www.networkupstools.org/ Network UPS Tools 05/21/2012 ONEAC(8)
All times are GMT -4. The time now is 02:06 AM.
Unix & Linux Forums Content Copyright 1993-2022. All Rights Reserved.
Privacy Policy