POWERMAN-PDU(8) 						    NUT Manual							   POWERMAN-PDU(8)

NAME
powerman-pdu - Driver for Powerman PDU SYNOPSIS
powerman-pdu -h powerman-pdu -a PDU_NAME [OPTIONS] Note This man page only documents the hardware-specific features of the powerman-pdu driver. For information about the core driver, see nutupsdrv(8). SUPPORTED HARDWARE
This driver supports a wide range of PDUs through the Powerman project. This includes various models from APC, Baytech, Cyclades, but also support IPMI and various blade management modules from HP, IBM and Sun. EXTRA ARGUMENTS
This driver doesn't support any optional settings. INSTALLATION
This driver is not built by default. You can build it by using "configure --with-powerman=yes". UPS COMMANDS
The following instant commands (see upscmd(8)) are available for each outlet of the PDU, with X standing for the outlet number: outlet.X.load.on Power on the outlet. outlet.X.load.off Power off the outlet. outlet.X.load.cycle Cycle the outlet (power off then power on, possibly with a delay). IMPLEMENTATION
The hostname of the Powerman server is specified using the "port" value in ups.conf, i.e.: [pdu] driver = powerman-pdu port = host.example.com:port The port used to reach powermand is optional if the default port is used. KNOWN ISSUES
In the current NUT version (2.4.1), ups.status is still exposed, with the value "WAIT". Some other values from the ups collection are also exposed. AUTHOR
Arnaud Quette <arnaud.quette@gmail.com> SEE ALSO
The core driver: nutupsdrv(8) Internet resources: The NUT (Network UPS Tools) home page: http://www.networkupstools.org/ The PowerMan home page: http://powerman.sourceforge.net/ Network UPS Tools 05/21/2012 POWERMAN-PDU(8)

Check Out this Related Man Page

CLONE(8)							    NUT Manual								  CLONE(8)

NAME
clone - UPS driver clone NOTE
This man page only documents the specific features of the clone driver. For information about the core driver, see nutupsdrv(8). DESCRIPTION
This driver, which sits on top of another driver socket, allows users to group clients to a particular outlet of a device and deal with this output as if it was a normal UPS. EXTRA ARGUMENTS
This driver supports the following settings: load.off=command Recommended. Set the command on the "real" UPS driver that will be used to switch off the outlet. You need both load.off and load.on in order to power cycle the outlet. Otherwise, shutting down the clients powered by an outlet is a one way street (see IMPORTANT). load.on=command Recommended. Set the command on the "real" UPS driver that will be used to switch on the outlet. You need both load.off and load.on in order to power cycle the outlet. Otherwise, shutting down the clients powered by an outlet is a one way street (see IMPORTANT). load.status=value Recommended. Set the variable on the "real" UPS driver that will be used to indicate the outlet status (i.e. on/off). If not specified, the clone driver will attempt to keep track of the outlet status, but this is less reliable. offdelay=num Set the timer (in seconds) before the outlet is turned off after the shutdown condition (OB LB) for this outlet is met or a command to shutdown was issued. Defaults to 120 seconds. ondelay=num Set the timer (in seconds) for the outlet to switch on in case the power returns after the oulet has been switched off. Defaults to 30 seconds. mincharge=value Set the remaining battery level when the clone UPS switches to LB (percent). minruntime=value Set the remaining battery runtime when the clone UPS switches to LB (seconds). IMPLEMENTATION
The port specification in the ups.conf(5) reference the driver socket that the "real" UPS driver is using. For example: [realups] driver = usbhid-ups port = auto [clone-outlet-1] driver = clone port = usbhid-ups-realups load.on = outlet.1.load.on load.off = outlet.1.load.off load.status = outlet.1.status [...] IMPORTANT
Unlike a real UPS, you should not configure a upsmon master for this driver. When a upsmon master sees the OB LB flags and tells the upsd server it is OK to initiate the shutdown sequence, the server will latch the FSD status and it will not be possible to restart the systems connected without restarting the upsd server. This will be a problem if the power returns after the clone UPS initiated the shutdown sequence on it's outlet, but returns before the real UPS begins shutting down. The solution is in the clone driver, that will insert the FSD flag if needed without the help of a upsmon master. CAVEATS
The clone UPS will follow the status on the real UPS driver. You can only make the clone UPS shutdown earlier than the real UPS driver, not later. If the real UPS driver initiates a shutdown, the clone UPS driver will immediately follow. Be aware that the commands to shutdown/restart an outlet on the real UPS drivers are not affected, so if you tell the real UPS driver to shutdown the outlet of the clone UPS driver, your clients will lose power without warning. AUTHOR
Arjen de Korte <adkorte-guest@alioth.debian.org> SEE ALSO
upscmd(1), upsrw(1), ups.conf(5), nutupsdrv(8) Internet Resources: The NUT (Network UPS Tools) home page: http://www.networkupstools.org/ Network UPS Tools 05/21/2012 CLONE(8)